MX Shunt Tripping Device

MX Shunt Tripping Device

MX shunt trip is mainly used for AC 50Hz,rated operating voltage of 230V line and combine with MCB  for long distance shunt trip operation.
Standard:IEC60947-5-1.

Get Quote
Technical Data

Technical parameter item

Parameter values

Rated control voltage Us

AC 230V 50Hz

Rated insulation voltage Ui

415V

Action characteristic

(70%~110%)Us,the tripper can operate reliably

life

not less than 4000 cycles

 

Normal working conditions and installation conditions

Ambient temperature:-5℃~40℃

Relative humidity:≤90%/25℃,≤50%/40℃

The altitude of the installation site shallnot exceed 2000m

        

                        